6.2
Embracing Challenge
Compact, self-controlling and mainte-
nance-free
With Jet-Stream heat exchanger avail-
able in 3 standard materials
Gas ow rate 1 stream 500 l/hr
Outlet dew point adjustable from +2 °C
to +15 °C
Dew point stability ± 0,1 °C
Status-Alarm contact standard
Small dimensions
Light weight
Optimum reliability
Special Features
Peltier-Gas Cooler Series ECP®
Version ECP 20-2 for 500 Nl/hr gas ow rate
(single stream)
ECP 20-2PV
Application
The M&C gas cooler ECP 20-2 is used in gas
analysis to lower the dew point of humid gas
to avoid condensation in the analyser. An
extremely stable gas dew point avoids water
vapour cross-sensitivity and volumetric errors.
Description
The electronically controlled peltier cooler
produced by M&C incorporates the ‘’Jet-
Stream design of heat exchanger. This design
induces condensate formation and guaran-
tees optimum dew point reduction to a sta-
ble low value, eliminating the need for addi-
tional pre-drainage devices.
The condensate formed should be removed
with a small peristaltic pump, sample trap
or collection vessel. The simple construction
employed enables heat exchangers of differ-
ent materials to be used depending on the
application.
The operating status of the cooler is displayed
by three LED’s, one each for over or under
temperature alarm and one which pulsates
indicating the cooler is functioning correctly.
The alarm status changes when the tempera-
ture deviates by +/-3 °C from the set point.
The gas cooler ECP 20-2 has got two EC-Jet-
stream heat exchangers which are best
employed using one as a pre-cooler and the
second as a main or final cooler with a flow
capacity max. of 500 Nl/hr.
The compact lightweight design of this
device makes it ideal for use in portable and
compact continuous sample conditioning
systems.
The gas cooler is self-controlling and mainte-
nance-free.
Technical specications and illustrations are without
obligation, subject to modications. 05.97/06.06
Vista de pagina 0
1 2 3

Indice de contenidos

Pagina 1 - (single stream)

M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany [email protected] • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 21

Pagina 2 - Sample outlet dew point °C

M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany [email protected] • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 21

Pagina 3 - Technical Data

M&C TechGroup Germany GmbH • Rehhecke 79 • 40885 Ratingen • Germany [email protected] • www.mc-techgroup.com • Fon +49 2102 935-0 • Fax +49 21

Comentarios a estos manuales

Sin comentarios